Efficiencies |
Flue
Gas Data at 10% excess air (2% O2) at 50% - 100% load |
Flue
Gas Data at 20% excess air (4% O2) at 50% - 100% load |
|||
|
Outlet |
Flue
Gas Amount kg/h per kW load |
Outlet |
Flue
Gas Amount kg/h per kW load |
||
|
88% 86% -2% +2% |
50% part load |
294 340 + 50 - 50 |
1,6506 1,6902 + 0,04 - 0,04 |
269 311 + 40 - 40 |
1,8162 1,8594 + 0,05 - 0,04 |
| The above
data can be used for
utilizing the waste heat in the flue gas - in
economizers etc
Example: |
UNDER CONSTRUCTION - UNDER UDARBEJDELSE
Ultra Compact Steam Generators · Marine Steam Generators Determine the flue gas arrangement
Type DT |
Heat |
Efficiency at 50% - 100% load % |
Flue Gas Data at 10% excess air (2% O2) at 50% - 100% load |
Flue Gas Data at 20% excess air (4% O2) at 50% - 100% load |
|||
|
Outlet |
Flue Gas Amount kg/h |
Outlet |
Flue Gas Amount kg/h |
||||
|
90% 88% 86% 84% |
Part
Load |
249 294 340 386 |
1,6146 1,6506 1,6902 1,7298 pr. kW |
228 269 311 352 |
1,7766 1,8162 1,8594 1,9044 pr. kW |
||
| 300 / 400 | 278 | 90% - 88% | |||||
| 400 / 600 | 417 | 90% - 88% | |||||
| 600 / 800 | 556 | 90% - 88% | |||||
| 800 / 1000 | 695 | 90% - 88% | |||||
| 1000 / 1250 | 869 | 90% - 88% | |||||
| 1200 / 1500 | 1.043 | 90% - 88% | |||||
| 1500 / 1800 | 1.390 | 90% - 88% | |||||
| 2000 / 2500 | 1.738 | 90% - 88% | |||||
| 2500 / 3000 | 1.800 | 90% - 88% | |||||
| 3000 / 4000 | 2.781 | 90% - 88% | |||||
| 4000 / 5000 | 3.476 | 90% - 88% | |||||
| 5000 / 6000 | 4.200 | 90% - 88% | |||||
|
Virkn. grad |
1,09 / 2 % |
kg/h pr. kW |
1,21 / 4 % |
kg/h pr. kW |
|
84 |
386 |
1,7298 |
352 |
1,9044 |
|
86 |
340 |
1,6902 |
311 |
1,8594 |
|
88 |
294 |
1,6506 |
269 |
1,8162 |
|
89 |
271 |
1,6326 |
248 |
1,7964 |
|
90 |
249 |
1,6146 |
228 |
1,7766 |